EngineeringMaterials Science

D. Tuckerman, R. Pease

1981.5.1IEEE ELECTRON DEVICE LETTERS

DOI: 10.1109/edl.1981.25367

tlooto Summary

Researchers design compact heat sink for VLSI with high performance forced liquid cooling.

Abstract

The problem of achieving compact, high-performance forced liquid cooling of planar integrated circuits has been investigated. The convective heat-transfer coefficient h between the substrate and the coolant was found to be the primary impediment to achieving low thermal resistance. For laminar flow in confined channels, h scales inversely with channel width, making microscopic channels desirable. The coolant viscosity determines the minimum practical channel width. The use of high-aspect ratio channels to increase surface area will, to an extent, further reduce thermal resistance. Based on these considerations, a new, very compact, water-cooled integral heat sink for silicon integrated circuits has been designed and tested. At a power density of 790 W/cm2, a maximum substrate temperature rise of 71°C above the input water temperature was measured, in good agreement with theory. By allowing such high power densities, the heat sink may greatly enhance the feasibility of ultrahigh-speed VLSI circuits.

Citation format

TUCKERMAN, D.; PEASE, R. High-performance heat sinking for VLSI. IEEE ELECTRON DEVICE LETTERS, 1981, 2: 126–129.