Please Don’t Blame Standard 62.1 for 1000 ppm CO2
A. Persily
2021.2.1ASHRAE JOURNAL
tlooto Summary
Indoor CO2 concentrations are misused as IAQ metrics, despite ASHRAE Standard 62.1 no longer having an indoor CO2 limit.
Abstract
Indoor concentrations of carbon dioxide (CO 2 ) have been widely promoted as metrics of indoor air quality (IAQ) and ventilation, in many cases without a sound explanation of what they are intended to characterize or an adequate discussion of the specific application and any limitations. Many practitioners and researchers use 1800 mg/m 3 (roughly 1000 ppm v ) as a criteria for defining good IAQ and cite ASHRAE Standard 62.1 (ASHRAE, 2019) as the source of this value. Standard 62.1 has not contained an indoor CO 2 limit for almost 30 years, and no current ASHRAE standard contains an indoor CO 2 limit. The CO 2 limit was removed from Standard 62.1 based on the confusion that it caused and the fact that it is not a good indicator of ventilation or IAQ. Numerous papers, presentations and workshops have attempted to clarify the significance of indoor CO 2 concentrations and even advocated that they not be used as IAQ or ventilation metrics. However, these efforts have not ended the confusion, and the attribution of a 1800 mg/m 3 limit to Standard 62.1 continues. This paper describes what Standard 62.1 says about CO 2 now, what it has said in the past, explains the basis for the 1800 mg/m 3 value, and stresses that the use of a CO 2 reference value to characterize ventilation rates must consider the building type and its occupancy.
Citation format
PERSILY, A. Please don’t blame standard 62.1 for 1000 ppm CO2. ASHRAE JOURNAL, 2021, 63: 1–2.